          Model

          VT3-X15

          VT3-X15D

          VT3-S12

          VT3-S12D

          VT3-S10

          VT3-V10

          VT3-V10D

          General specifications

          Current consumption

          -

          1800mA or less

          -

          1100mA or less

          -

          1000mA or less

          Power consumption

          110VA or less

          -

          70VA or less

          -

          65VA or less

          -

          Structure

          Panel built-in type, IP65f equivalent dust-proof, waterjet-proof on only front panel

          Overvoltage category

          II

          I

          II

          I

          II

          I

          Pollution degree

          2

          Power voltage

          100 to 240 VAC±10% (50/60 Hz)

          24 VDC ±10%

          100 to 240 VAC±10% (50/60 Hz)

          24 VDC ±10%

          100 to 240 VAC ±10% (50/60 Hz)

          100 to 240 VAC±10% (50/60 Hz)

          24 VDC ±10%

          Noise resistance

          1500 Vp-p pulse width 1 µs (common mode, based on noise simulator)

          Withstand voltage

          1500 VAC 1 minute (between power terminal and housing)

          Insulation resistance

          50 MΩ or more tested by 500 VDC megohmmeter (between power terminal and housing)

          Vibration resistance

          Intermittent vibration

          Frequency: 5 to 9 Hz

          Half amplitude: 3.5 mm*1

          Frequency: 9 to 150 Hz

          Acceleration: 9.8 m/s2*1

          Continuous vibration

          Frequency: 5 to 9 Hz

          Half amplitude: 1.75 mm*1

          Frequency: 9 to 150 Hz

          Acceleration: 4.9 m/s2 *1

          Ground

          Class D grounding
          (Class 3 grounding).

          Class D grounding (Class 3 grouding).

          Class D grounding (Class 3 grounding).

          Class D grounding (Class 3 grouding).

          Class D grounding (Class 3 grounding).

          Class D grounding (Class 3 grouding).

          Operating environment

          Minimal amount of dust and corrosive gas present

          Ambient operating temperature

          0 to +50°C

          Ambient operating humidity

          35 to 85%RH (No condensation)*2

          Ambient storage temperature

          -10 to +60°C (No freezing)

          Ambient storage humidity

          35 to 85%RH (No condensation)*2

          Weight

          Approx 4750 g

          Approx 4500 g

          Approx 2600 g

          Approx 2500 g

          Approx 2300 g

          Approx 2200 g

          Performance specifications

          Displaypanel

          Display elements

          TFT colour LCD

          Display colour

          32768 colours

          Number of points displayed

          W 1024 × H 768 points

          W 800 × H 600 points

          W 640 × H 480 points

          Active display area

          W 304.1 × H 228.1 mm

          W 246.0 × H 184.5 mm

          W 211.2 × H 158.4 mm

          Service life (normal temperature andhumidity)

          Approx 50000 h

          Backlightlamp

          System

          White LED (Not replaceable)*3

          Life-span

          Approx 50000 h

          Touchswitch

          Number of switches

          64×48/screen

          50×38/screen

          40×30/screen

          System

          Analogue resistive membrane type

          Matrix resistive film

          Operating force

          1.96N or less

          0.98N or less

          Life-span

          1,000,000 times or more

          Screen data internal memory

          Memory capacity

          28 MB (44 MB expansible)

          12 MB (28 MB when extended)

          Number of pages that can be registered

          Up to 1024 pages

          Number of screens that can be registered

          Up to 1024 screens

          Page No.: 0 to 8999, Global window No.: G000 to G999, Report screen P.00 to P.15

          Data backup

          Screen data

          Flash ROM can be erased 100000 times

          Recording data

          SRAM backup:lithium battery

          Character font

          Outline font, Bitmap font, Stroke font Windows font, IMAGE font, Small font

          Calendar timer

          Accuracy: ±40s/month (25°C), Backup:lithium battery (5 years above of service life at 25°C)

          Communication function

          PLC host link

          KEYENCE, Mitsubishi Electric, OMRON, Sharp, Fuji Electric FA Components & Systems, Yaskawa Electric, Hitachi, Panasonic Electric Works, JTEKT (Toyota),
          Koyo Electronics Industries, Yokogawa Electric, Toshiba, Toshiba Machine, Fanuc, GE Fanuc Automation, Rockwell (Allen Bradley), Siemens

          Thermostat

          Yokogawa Electric, Azbil (Yamatake), OMRON, RKC Instrument, Shinko Technos, CHINO

          Inverter

          Mitsubishi Electric, Fuji Electric FA Components & Systems, Yaskawa Electric, OMRON

          Servo amplifier

          Mitsubishi Electric

          Stepping motor

          Oriental Motor

          Robot controller

          IAI

          Eco-power meter

          Panasonic Electric Works

          General-purpose communication

          Based on specific commands

          I/O specifications

          Serial I/F (PORT 1: SERIAL) for connecting PCs

          Applied standard

          Conforms to EIA RS-232C

          Synchronisation between the transmitter and receiver

          Start-stop, full duplex

          Communication distance

          15m

          Data length

          7 or 8 bits

          Parity

          Even, odd, none

          Communication speed

          1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

          Serial I/F (PORT 2) for connecting PLC/external devices

          Applied standard

          Conforms to EIA RS-232C and RS-422A

          Synchronisation between the transmitter and receiver

          Start-stop, full duplex

          Communication distance

          15m (RS-232C)/500m (RS-422A)

          Data length

          7 or 8 bits

          Parity

          Even, odd, none

          Communication speed

          1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

          Serial I/F (PORT 3) for connecting barcode/PLC/external devices

          Applied standard

          Conforms to EIA RS-232C*4

          Synchronisation between the transmitter and receiver

          Start-stop, full duplex

          Communication distance

          15 m*5

          Data length

          7 or 8 bits

          Parity

          Even, odd, none

          Communication speed

          1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

          Serial I/F (PORT 4) for connecting MegaLink/multi-link/KL-link/external devices

          When connected through MegaLink

          Applied standard

          RS-485

          Synchronisation between the transmitter and receiver

          Start-stop, half duplex

          Communication speed

          19,200 bps, 115,200 bps, 0.5 Mbps, 1 Mbps, 2 Mbps

          19,200 bps, 115,200 bps, 0.5 Mbps, 1M bps, 2 Mbps

          19,200 bps, 115,200 bps, 0.5 Mbps, 1 Mbps, 2 Mbps

          19,200 bps, 115,200 bps, 0.5 Mbps, 1M bps, 2 Mbps

          Cable connection

          Multi-drop (branching is not possible)

          Maximum number of connectable units

          15

          Baud rate 19200

          Maximum extension distance: 1,000 m

          Baud rate 115200

          Baud rate 0.5 M

          Maximum extension distance: 500 m

          Baud rate 1 M

          Maximum extension distance: 200 m

          Baud rate 2 M

          Maximum extension distance: 100 m

          When connected through VT2 multi-link

          Applied standard

          RS-485

          Synchronisation between the transmitter and receiver

          Start-stop, half duplex

          Communication distance

          Maximum extension distance: 500 m or less

          Communication speed

          19200, 115200, 0.5M, 1M bit/s

          Baud rate 115200 or less

          Maximum extension distance: 500 m

          Baud rate 0.5 M

          Maximum extension distance: 100 m

          Baud rate 1 M

          Maximum extension distance: 50 m

          When connected through multi-link

          Applied standard

          RS-485

          Synchronisation between the transmitter and receiver

          Start-stop, half duplex

          Communication distance

          Maximum extension distance: 500 m or less

          Communication speed

          19200, 38400, 57600, 115200 bit/s

          When linked with the KL

          Sign system

          f, f/2 encoding

          Control method

          Autonomous distributed token bus control

          Cable connection

          T-shaped branch, multi-drop

          Communication speed

          5 Mbps, 2.5 Mbps, 625 kbps, 156 kbps

          Communication media

          Dedicated cable KPEV-SB (1 pc; 2-core shielded twisted pair cable [stranded wire]) * Conductor section area: 0.5 to 1.25 mm2

          Maximum number of connectable units

          129 units (including the master station, not including the KL-T1)

          Error control

          Vertical parity, checksum, double sampling, burst noise detection

          Baud rate 5 Mbit/s: Maximum base length

          50 m

          Baud rate 5 Mbit/s: Maximum branch wire length

          20 m

          Baud rate 2.5 Mbit/s: Maximum base length

          120 m

          Baud rate 2.5 Mbit/s: Maximum branch wire length

          40 m

          Baud rate 625 kbit/s: Maximum base length

          500 m

          Baud rate 625 kbit/s: Maximum branch wire length

          150 m

          Baud rate 156 kbit/s: Maximum base length

          1200 m

          Baud rate 156 kbit/s: Maximum branch wire length

          350 m

          Communication cable conductor section area 0.5 mm2

          Maximum extension distance: 1,000 m

          Communication cable conductor section area 0.75 mm2

          Maximum extension distance: 1,200 m

          Communication cable conductor section area 0.9 mm2

          Communication cable conductor section area 1.25 mm2

          *1 Conforms to JIS B 3502, IEC61131-2
          Number of sweeps: 10 times respectively in the X, Y, and Z directions (100 minutes)
          *2 When the ambient temperature is higher than 40°C, please use it in the condition of an absolute humidity of 85%RH at 40°C.
          *3 Cold-cathode tube (Replaceable)
          *4 Pin number 9 is assigned to 5 VDC. Do not connect this pin when connecting to a PLC or to a type of barcode reader that supplies a dedicated power source.
          *5 This is when a separate power supply is used for the barcode reader and when a PLC is connected.

          Model

          VT3-V8

          VT3-V7

          VT3-V7R

          General specifications

          Current consumption

          950mA or less

          800mA or less

          550mA or less

          Structure

          Panel built-in type, IP65f equivalent dust-proof, waterjet-proof
          on only front panel

          IP65f equivalent dust proof, waterjet proof

          Overvoltage category

          I

          Pollution degree

          2

          3

          Power voltage

          24 VDC ±10%

          Noise resistance

          1500 Vp-p pulse width 1 µs 50 ns (common mode, based on noise simulator)

          Withstand voltage

          1500 VAC 1 minute (between power terminal and housing)

          Insulation resistance

          50 MΩ or more tested by 500 VDC megohmmeter (between power terminal and housing)

          Vibration resistance

          Intermittent vibration

          Frequency: 5 to 9 Hz

          Half amplitude:3.5 mm*1

          Frequency: 9 to 150 Hz

          Acceleration: 9.8 m/s2 *1

          Continuous vibration

          Frequency: 5 to 9 Hz

          Half amplitude:1.75 mm*1

          Frequency: 9 to 150 Hz

          Acceleration: 4.9 m/s2 *1

          Ground

          Class D grounding (Class 3 grouding).

          Operating environment

          Minimal amount of dust and corrosive gas present

          Ambient operating temperature

          0 to +50°C

          Ambient operating humidity

          35 to 85%RH (No condensation)*2

          Ambient storage temperature

          -10 to +60°C (No freezing)

          Ambient storage humidity

          35 to 85%RH (No condensation)*2

          Weight

          Approx 1250 g

          Approx 1150 g

          Approx 1,600 g (excluding the cable)

          Performance specifications

          Displaypanel

          Display elements

          TFT colour LCD

          Display colour

          32768 colours

          Number of points displayed

          W 640 × H 480 points

          Active display area

          W 170.9 × H 128.2 mm

          W 151.7 × H 113.8 mm

          Service life (normal temperature andhumidity)

          Approx 50000 h

          Backlightlamp

          System

          White LED (Not replaceable)*3

          Cold-cathode tube (Not replaceable)

          Life-span

          Approx 50000 h

          Approx 54000 h

          Touchswitch

          Number of switches

          40×30/screen

          System

          Matrix resistive film

          Operating force

          0.98N or less

          Life-span

          1,000,000 times or more

          External calibration input signal

          Pressure-sensitive type

          Screen data internal memory

          Memory capacity

          12 MB (memory extension enabled)

          Number of pages that can be registered

          Up to 1024 pages

          Number of screens that can be registered

          Up to 1024 screens

          Page No.: 0 to 8999, Global window No.: G000 to G999, Report screen P.00 to P.15

          Data backup

          Screen data

          Flash ROM can be erased 100000 times.

          Recording data

          SRAM backup:lithium battery

          Character font

          Outline font, Bitmap font, Stroke font Windows font, IMAGE font, Small font

          Calendar timer

          Accuracy: ±40s/month (25°C), Backup:lithium battery (5 years above of service life at 25°C)

          Communication function

          PLC host link

          KEYENCE, Mitsubishi Electric, OMRON, Sharp, Fuji Electric FA Components & Systems, Yaskawa Electric, Hitachi, Panasonic Electric Works, JTEKT (Toyota),
          Koyo Electronics Industries, Yokogawa Electric, Toshiba, Toshiba Machine, Fanuc, GE Fanuc Automation, Rockwell (Allen Bradley), Siemens

          Thermostat

          Yokogawa Electric, Azbil (Yamatake), OMRON, RKC Instrument, Shinko Technos, CHINO

          Inverter

          Mitsubishi Electric, Fuji Electric FA Components & Systems, Yaskawa Electric, OMRON

          Servo amplifier

          Mitsubishi Electric

          Stepping motor

          Orienltal Motor

          Robot controller

          IAI

          Eco-power meter

          Panasonic Electric Works

          General-purpose communication

          Based on specific commands

          Grip switch

          Life-span

          50,000 times or more

          Arrow keys

          100,000 times or more

          I/O specifications

          Serial I/F (PORT 1: SERIAL) for connecting PCs

          Applied standard

          Conforms to EIA RS-232C

          Synchronisation between the transmitter and receiver

          Start-stop, full duplex

          Communication distance

          15m

          Data length

          7 or 8 bits

          Parity

          Even, odd, none

          Communication speed

          1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

          Serial I/F (PORT 2) for connecting PLC/external devices

          Applied standard

          Conforms to EIA RS-232C and RS-422A

          Synchronisation between the transmitter and receiver

          Start-stop, full duplex

          Communication distance

          15m (RS-232C)/500m (RS-422A)

          Data length

          7 or 8 bits

          Parity

          Even, odd, none

          Communication speed

          1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

          Serial I/F (PORT 3) for connecting barcode/PLC/external devices

          Applied standard

          Conforms to EIA RS-232C*4

          Synchronisation between the transmitter and receiver

          Start-stop, full duplex

          Communication distance

          15 m*5

          Data length

          7 or 8 bits

          Parity

          Even, odd, none

          Communication speed

          1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

          Serial I/F (PORT 4) for connecting MegaLink/multi-link/KL-link/external devices

          When connected through MegaLink

          Applied standard

          RS-485

          Synchronisation between the transmitter and receiver

          Start-stop, half duplex

          Communication speed

          19,200 bps, 115,200 bps, 0.5 Mbps, 1 Mbps, 2 Mbps

          Cable connection

          Multi-drop (branching is not possible)

          Maximum number of connectable units

          15

          Baud rate 19200

          Maximum extension distance: 1,000 m

          Baud rate 115200

          Baud rate 0.5 M

          Maximum extension distance: 500 m

          Baud rate 1 M

          Maximum extension distance: 200 m

          Baud rate 2 M

          Maximum extension distance: 100 m

          When connected through VT2 multi-link

          Applied standard

          RS-485

          Synchronisation between the transmitter and receiver

          Start-stop, half duplex

          Communication distance

          Maximum extension distance: 500 m or less

          Communication speed

          19200, 115200, 0.5M, 1M bit/s

          Baud rate 115200 or less

          Maximum extension distance: 500 m

          Baud rate 0.5 M

          Maximum extension distance: 100 m

          Baud rate 1 M

          Maximum extension distance: 50 m

          When connected through multi-link

          Applied standard

          RS-485

          Synchronisation between the transmitter and receiver

          Start-stop, half duplex

          Communication distance

          Maximum extension distance: 500 m or less

          Communication speed

          19200, 38400, 57600, 115200 bit/s

          When linked with the KL

          Sign system

          f, f/2 encoding

          Control method

          Autonomous distributed token bus control

          Cable connection

          T-shaped branch, multi-drop

          Communication speed

          5 Mbps, 2.5 Mbps, 625 kbps, 156 kbps

          Communication media

          Dedicated cable KPEV-SB (1 pc; 2-core shielded twisted pair cable [stranded wire]) * Conductor section area: 0.5 to 1.25 mm2

          Maximum number of connectable units

          129 units (including the master station, not including the KL-T1)

          Error control

          Vertical parity, checksum, double sampling, burst noise detection

          Baud rate 5 Mbit/s: Maximum base length

          50 m

          Baud rate 5 Mbit/s: Maximum branch wire length

          20 m

          Baud rate 2.5 Mbit/s: Maximum base length

          120 m

          Baud rate 2.5 Mbit/s: Maximum branch wire length

          40 m

          Baud rate 625 kbit/s: Maximum base length

          500 m

          Baud rate 625 kbit/s: Maximum branch wire length

          150 m

          Baud rate 156 kbit/s: Maximum base length

          1200 m

          Baud rate 156 kbit/s: Maximum branch wire length

          350 m

          Communication cable conductor section area 0.5 mm2

          Maximum extension distance: 1,000 m

          Communication cable conductor section area 0.75 mm2

          Maximum extension distance: 1,200 m

          Communication cable conductor section area 0.9 mm2

          Communication cable conductor section area 1.25 mm2

          *1 Conforms to JIS B 3502, IEC61131-2
          Number of sweeps: 10 times respectively in the X, Y, and Z directions (100 minutes)
          *2 When the ambient temperature is higher than 40°C, please use it in the condition of an absolute humidity of 85%RH at 40°C.
          *3 Cold-cathode tube (Replaceable)
          *4 Pin number 9 is assigned to 5 VDC. Do not connect this pin when connecting to a PLC or to a type of barcode reader that supplies a dedicated power source.
          *5 This is when a separate power supply is used for the barcode reader and when a PLC is connected.

          Model

          VT3-V6H

          VT3-V6HG

          VT3-Q5H

          VT3-Q5HG

          General specifications

          Current consumption

          380mA or less

          250mA or less

          Structure

          IP65f equivalent dust proof, waterjet proof

          Overvoltage category

          I

          Pollution degree

          3

          Power voltage

          24 VDC ±10%

          Noise resistance

          1500 Vp-p pulse width 1 µs 50 ns (common mode, based on noise simulator)

          Withstand voltage

          1500 VAC 1 minute (between power terminal and housing)

          Insulation resistance

          50 MΩ or more tested by 500 VDC megohmmeter (between power terminal and housing)

          Vibration resistance

          Intermittent vibration

          Frequency: 5 to 9 Hz

          Half amplitude:3.5 mm*1

          Frequency: 9 to 150 Hz

          Acceleration: 9.8 m/s2*1

          Continuous vibration

          Frequency: 5 to 9 Hz

          Half amplitude:1.75 mm*1

          Frequency: 9 to 150 Hz

          Acceleration: 4.9 m/s2 *1

          Ground

          Class D grounding (Class 3 grouding).

          Operating environment

          Minimal amount of dust and corrosive gas present

          Ambient operating temperature

          0 to +50°C *2*3

          0 to +50°C*3

          Ambient operating humidity

          35 to 85%RH (No condensation)*4*3

          Ambient storage temperature

          -10 to +60°C (No freezing)

          Ambient storage humidity

          35 to 85%RH (No condensation)*4*3

          Drop

          According to JIS B 3502 IEC61131-2 (1.3m)

          Weight

          Approx 1100g*5

          Approx 1120 g*5

          Approx 970g*5

          Approx 990g*5

          Performance specifications

          Displaypanel

          Display elements

          TFT colour LCD

          Display colour

          32768 colours

          Number of points displayed

          W 640 × H 480 points

          W 320 × H 240 points

          Active display area

          W 132.5 × H 99.4 mm

          W 115.2 × H 86.4 mm

          Service life (normal temperature andhumidity)

          Approx 50000 h

          Backlightlamp

          System

          White LED (Not replaceable)

          Life-span

          Approx 50000 h

          Touchswitch

          Number of switches

          80×60/screen

          40×30/screen

          System

          Analogue resistive membrane type

          Operating force

          0.98N or less

          Life-span

          1,000,000 times or more

          Screen data internal memory

          Memory capacity

          12 MB (memory extension enabled)

          4 MB (memory extension enabled)

          Number of pages that can be registered

          Up to 1024 pages

          Number of screens that can be registered

          Up to 1024 screens

          Page No.: 0 to 8999, Global window No.: G000 to G999, Report screen P.00 to P.15

          Data backup

          Screen data

          Flash ROM can be erased 100000 times.

          Recording data

          SRAM backup:lithium battery

          Character font

          Outline font, Bitmap font, Stroke font Windows font, IMAGE font, Small font

          Calendar timer

          Accuracy: ±40s/month (25°C), Backup:lithium battery (5 years above of service life at 25°C)

          Communication function

          PLC host link

          KEYENCE, Mitsubishi Electric, OMRON, Sharp, Fuji Electric FA Components & Systems, Yaskawa Electric, Hitachi, Panasonic Electric Works, JTEKT (Toyota),
          Koyo Electronics Industries, Yokogawa Electric, Toshiba, Toshiba Machine, Fanuc, GE Fanuc Automation, Rockwell (Allen Bradley), Siemens

          Thermostat

          Yokogawa Electric, Azbil (Yamatake), OMRON, RKC Instrument, Shinko Technos, CHINO

          Inverter

          Mitsubishi Electric, Fuji Electric FA Components & Systems, Yaskawa Electric, OMRON

          Servo amplifier

          Mitsubishi Electric

          Stepping motor

          Orienltal Motor

          Robot controller

          IAI

          Eco-power meter

          Panasonic Electric Works

          General-purpose communication

          Based on specific commands

          I/O specifications

          Function switch (FSW1/FSW2/FSW5/FSW6)

          Number of outputs

          4 (FSW1, FSW2, FSW5, FSW6)

          Common terminal

          4 terminals/common (FSWC)

          Output

          MOSFET (N-ch; with overcurrent protection function)

          Rated load

          30 VDC 0.1 A

          Leakage current (at OFF)

          100 µA or less

          Residual voltage (at ON)

          1.0V or less

          Durability

          300,000 times or more

          Enabling switch (EN1A/EN1B/EN2A/EN2B)

          Rated voltage

          30 VCD

          30 VDC

          30 VCD

          30 VDC

          Rated current

          1 A (resistive load), 0.7 A (inductive load)

          1 A (resistive load), 0.7 A (inductive load)

          Contact method

          2a contact

          2a contact

          Durability

          Mechanical

          Position 1 -> 2 -> 1: 1,000,000 times or more, position 1 -> 2 -> 3 -> 1: 100,000 times or more

          Position 1 -> 2 -> 1: 1,000,000 times or more, position 1 -> 2 -> 3 -> 1: 100,000 times or more

          Electrical

          100,000 times or more

          100,000 times or more

          Function

          The following 3-position-operation is available: position 1: off (when not pressed), position 2: on (when pressed to the middle position), position 3: off (when pressed as far as possible). * When the position returns from position 3 (when pressed as far

          The following 3-position-operation is available: position 1: off (when not pressed), position 2: on (when pressed to the middle position), position 3: off (when pressed as far as possible). * When the position returns from position 3 (when pressed as far

          RS-232C/422 communication (CN2A/CN2B)

          Applied standard

          Conforms to EIA RS-232C and RS-422

          Synchronisation between the transmitter and receiver

          Start-stop, full duplex

          Communication distance

          15m (RS-232C)/500m (RS-422)

          Data length

          7 or 8 bits

          Parity

          Even, odd, none

          Communication speed

          1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

          Ethernet communication (CN3)

          Compliance

          IEEE802.3

          Transmission speed

          10 Mbps (10BASE-T),100 Mbps (100BASE-TX)

          Transmission medium

          STP or category 3 or higher UTP (10BASE-T), STP or category 5 or higher UTP (100BASE-TX)*6

          Maximum cable length

          100 m

          Maximum number of connectable hubs

          4 (10BASE-T),2 (100BASE-TX)

          Maximum number of connections

          PC application:*7 3,
          FTP: 4

          MegaLink/multi-link (A/B/G)

          When connected through MegaLink

          Applied standard

          RS-485

          Synchronisation between the transmitter and receiver

          Start-stop, half duplex

          Communication speed

          19,200 bps, 115,200 bps, 0.5 Mbps, 1 Mbps, 2 Mbps

          Cable connection

          Multi-drop (branching is not possible)

          Maximum number of connectable units

          15

          Baud rate 19200

          Maximum extension distance: 1,000 m

          Baud rate 115200

          Baud rate 0.5 M

          Maximum extension distance: 500 m

          Baud rate 1 M

          Maximum extension distance: 200 m

          Baud rate 2 M

          Maximum extension distance: 100 m

          When connected through VT multi-link

          Applied standard

          RS-485

          Synchronisation between the transmitter and receiver

          Start-stop, half duplex

          Communication distance

          Maximum extension distance: 500 m or less

          Communication speed

          19200, 115200, 0.5M, 1M bit/s

          Baud rate 115200 or less

          Maximum extension distance: 500 m

          Baud rate 0.5 M

          Maximum extension distance: 100 m

          Baud rate 1 M

          Maximum extension distance: 50 m

          When connected through multi-link

          Applied standard

          RS-485

          Synchronisation between the transmitter and receiver

          Start-stop, half duplex

          Communication distance

          Maximum extension distance: 500 m or less

          Communication speed

          19200, 38400, 57600, 115200 bit/s

          *1 Conforms to JIS B 3502, IEC61131-2
          Number of sweeps: 10 times respectively in the X, Y, and Z directions (100 minutes)
          *2 Please use the unit in the condition of the ambient temperature at 0 to 40°C when the back light power is set to “”.
          *3 Use this product under the condition that if the ambient temperature exceeds 40°C, the absolute humidity is 40°C 85% RH or less.
          *4 When the ambient temperature is higher than 40°C, please use it in the condition of an absolute humidity of 85%RH at 40°C.
          *5 Excluding individual unit and cable.
          *6 STP = shielded twisted pair cable, UTP = unshielded twisted pair cable
          *7 PC application refers to VT STUDIO and DATA BUILDER.

          Model

          VT3-W4T

          VT3-W4TA

          VT3-W4M

          VT3-W4MA

          VT3-W4G

          VT3-W4GA

          General specifications

          Current consumption

          200mA or less

          Structure

          Panel built-in type, IP65f equivalent dust-proof, waterjet-proof on only front panel

          Overvoltage category

          I

          Pollution degree

          2

          Power voltage

          24 VDC ±10%

          Noise resistance

          1500 Vp-p pulse width 1 µs (common mode, based on noise simulator)

          Withstand voltage

          1500 VAC 1 minute (between power terminal and housing)

          Insulation resistance

          50 MΩ or more tested by 500 VDC megohmmeter (between power terminal and housing)

          Vibration resistance

          Intermittent vibration

          Frequency: 5 to 9 Hz

          Half amplitude:3.5 mm*1

          Frequency: 9 to 150 Hz

          Acceleration:9.8 m/s2 *1

          Continuous vibration

          Frequency: 5 to 9 Hz

          Half amplitude:1.75 mm*1

          Frequency: 9 to 150 Hz

          Acceleration:4.9 m/s2 *1

          Operating environment

          Minimal amount of dust and corrosive gas present

          Ambient operating temperature

          0 to +50°C

          Ambient operating humidity

          35 to 85%RH (No condensation)*2

          Ambient storage temperature

          -20 to +60°C (No freezing)

          Ambient storage humidity

          35 to 85%RH (No condensation)*2

          Weight

          Approx 250 g

          Performance specifications

          Displaypanel

          Display elements

          TFT colour LCD

          STN black/white LCD

          Display colour

          32768 colours

          32-gradation gray scale

          Number of points displayed

          W 320 × H 128 points

          Active display area

          W 110.4 × H 44.2 mm

          W 99.2 × H 39.7 mm

          Service life (normal temperature andhumidity)

          Approx 50000 h

          Backlightlamp

          System

          White LED (Not replaceable)

          white/red LED (Not replaceable)

          Green/Red LED (Not replaceable)

          Life-span

          Approx 50000 h

          Display colour

          3 colours (white, red, peach)

          3 colours (green, red, orange)

          Touchswitch

          Number of switches

          40×16/screen

          System

          Analogue resistive membrane type

          Operating force

          0.98N or less

          Life-span

          1,000,000 times or more

          Screen data internal memory

          Memory capacity

          3 MB

          Number of pages that can be registered

          Up to 1024 pages

          Number of screens that can be registered

          Up to 1024 screens

          Page No.: 0 to 8999, Global window No.: G000 to G999

          Data backup

          Screen data

          Flash ROM can be erased for 100000 times

          Recording data

          SRAM backup:lithium battery

          Character font

          Outline font, Bitmap font, Windows font, IMAGE font, Small font

          Calendar timer

          Accuracy:±40s/month (25°C), Backup:1lithium battery (5 years above of service life at 25°C)

          Communication function

          PLC host link

          KEYENCE, Mitsubishi Electric, OMRON, Sharp, Fuji Electric FA Components & Systems, Yaskawa Electric, Hitachi, Panasonic Electric Works, JTEKT (Toyota),
          Koyo Electronics Industries, Yokogawa Electric, Toshiba, Toshiba Machine, Fanuc, GE Fanuc Automation, Rockwell (Allen Bradley), Siemens

          Thermostat

          Yokogawa Electric, Azbil (Yamatake), OMRON, RKC Instrument, Shinko Technos, CHINO

          Inverter

          Mitsubishi Electric, Fuji Electric FA Components & Systems, Yaskawa Electric, OMRON

          Servo amplifier

          Mitsubishi Electric

          Stepping motor

          Oriental Motor

          Robot controller

          IAI

          Eco-power meter

          Panasonic Electric Works

          General-purpose communication

          Based on specific commands

          I/O specifications

          Serial I/F (PORT 2) for connecting PLC/MegaLink/multi-link/external devices

          Applied standard

          Conforms to EIA RS-422A and RS-485

          Conforms to EIA RS-422A and RS-485

          Conforms to EIA RS-422A and RS-485

          Synchronisation between the transmitter and receiver

          RS-422A: start-stop, full duplex; RS-485: start-stop, half duplex

          RS-422A: start-stop, full duplex; RS-485: start-stop, half duplex

          RS-422A: start-stop, full duplex; RS-485: start-stop, half duplex

          Transmission distance

          RS-422A: 500 m, RS-485: 1,000 m

          RS-422A: 500 m, RS-485: 1,000 m

          RS-422A: 500 m, RS-485: 1,000 m

          Data length

          7 or 8 bits

          7 or 8 bits

          7 or 8 bits

          Parity

          Even, odd, none

          Even, odd, none

          Even, odd, none

          Transmission speed

          1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

          1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

          1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

          When connected through MegaLink

          Applied standard

          RS-485

          Synchronisation between the transmitter and receiver

          Start-stop, half duplex

          Start-stop, half duplex

          Start-stop, half duplex

          Communication speed

          19,200, 115,200 bps

          19,200, 115,200 bps

          19,200, 115,200 bps

          Connection format

          Multi-drop (branching is not possible)

          Multi-drop (branching is not possible)

          Multi-drop (branching is not possible)

          Maximum number of connectable units

          15

          15

          15

          Baud rate 19200

          Maximum extension distance: 1,000 m

          Maximum extension distance: 1,000 m

          Maximum extension distance: 1,000 m

          Baud rate 115200

          When connected through VT2 multi-link

          Communication speed

          19,200, 115,200 bps

          19,200, 115,200 bps

          19,200, 115,200 bps

          When connected through multi-link

          Applied standard

          RS-485

          RS-485

          RS-485

          Synchronisation between the transmitter and receiver

          Start-stop, half duplex

          Start-stop, half duplex

          Start-stop, half duplex

          Communication distance

          Maximum extension distance: 500 m or less

          Maximum extension distance: 500 m or less

          Maximum extension distance: 500 m or less

          Communication speed

          19,200, 38,400, 57,600, 115,200 bps

          19,200, 38,400, 57,600, 115,200 bps

          19,200, 38,400, 57,600, 115,200 bps

          Serial I/F (PORT 2) for connecting PLC/external devices

          Applied standard

          Conforms to EIA RS-232C

          Conforms to EIA RS-232C

          Conforms to EIA RS-232C

          Synchronisation between the transmitter and receiver

          Start-stop, half duplex

          Start-stop, half duplex

          Start-stop, half duplex

          Communication distance

          15m

          Data length

          7 or 8 bits

          7 or 8 bits

          7 or 8 bits

          Parity

          Even, odd, none

          Even, odd, none

          Even, odd, none

          Communication speed

          1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

          1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

          1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

          *1 Conforms to JIS B 3502, IEC61131-2
          Number of sweeps: 10 times respectively in the X, Y, and Z directions (100 minutes)
          *2 When the ambient temperature is higher than 40°C, please use it in the condition of an absolute humidity of 85%RH at 40°C.

          • PLC/HMI User Support
          • Trade Shows and Exhibitions
          • eNews Subscribe

          Controls