Programmable ControllerKV-5000/3000 series

KL-WH1

Power Measurement Unit

SPECIFICATIONS

Select Language

Model

KL-WH1

Performance specifications

Number of channels

1CH

Input voltage

100 to 250 VAC (sine wave), 50/60 Hz

Power consumption

10VA or less

Phase wire type

3-phase 3-wire, single-phase 2-wire, single-phase 3-wire

Measurement items

Demand value, instantaneous active power, instantaneous reactive power, active power, reactive power, phase-to-phase voltage, phase current, power factor, frequency

Power voltage

100 to 220 VAC ┬▒ 10%, 50/60 Hz

Current measurement

Optional external current sensors (three types for the CT: 50 A, 100 A, and 250 A) are available. Use the setting switch to select the current setting.

Power off memory

Non-volatile memory (integrated active power and reactive power)

Integrated value clear

Use the front panel key switch, control input terminal, or KL to provide the clear instruction.

Weight

approx 400g