Recent Searches
    Series ()
      Models ()
        Keywords

          Programmable ControllerKV-5000/3000 series

          KV-C64XB

          64-point Connector, with All Terminals Supporting 2-wire Sensors

          SPECIFICATIONS

          Select Language

          Model

          KV-C64XB

          Type

          Input unit

          External connection mode

          Connector (MIL standard)*1

          Input

          Number of inputs

          64 points

          Input mode

          DC 24 V mode*2

          Max. input voltage

          DC 26.4 V (±10 %)

          Rated input voltage

          DC 24 V, 4.1 mA

          Min. ON voltage

          19 V

          Max. OFF current

          1.5 mA

          Common point mode

          32 points/1 common (4 terminals)*3

          Input time constant

          [Constant at input setting 25µs] OFF to ON: TYP 25 µs/MAX 65 µs、ON to OFF: TYP 75 µs/MAX 120 µs
          [Constant at input setting 1 ms] OFF to ON: TYP 1 ms/MAX 1.2 ms、ON to OFF: TYP 1 ms/MAX 1.2 ms
          [Constant at input setting 10 ms] OFF to ON: TYP 10 ms/MAX 12 ms、ON to OFF: TYP 10 ms/MAX 12 ms
          (switchable among 3 levels)

          Input impedance

          5.6 kΩ

          Internal current consumption

          25 mA or less

          Weight

          Approx. 140 g

          *1 In conformity with MIL-C-83503.
          *2 2-wire type supported on all terminals (not supported on 2-wire type proximity sensor EV series)
          *3 Although the KV-C64XA/C64XB has 4 COM points, internally there is an H-side (2 points) and an L-side (2 points) that share a common circuit.