          KV-C64XC

          64-point Connector

          SPECIFICATIONS

          Select Language

          Model

          KV-C64XC

          Type

          Input unit

          External connection mode

          Connector (MIL specification)*1

          Input

          Number of inputs

          64 points

          Input mode

          24 VDC mode*2

          Max. input voltage

          26.4 VDC

          Rated input voltage

          24 VDC 4.1 mA

          Min. ON voltage

          19 V

          Max. OFF current

          1.5 mA

          Max. OFF voltage

          -

          Common point mode

          32 points/1 common point (4 terminals)*3

          Input time constant

          [Input time constant setting 25 µs] OFF to ON: TYP 25 µs/MAX 65 µs, ON to OFF: TYP 75 µs/MAX 120 µs
          [Input time constant setting 300 µs*4] OFF to ON: TYP 275 µs/MAX 365 µs, ON to OFF: TYP 275 µs/MAX 420 µs
          [Input time constant setting 1 ms] OFF to ON: TYP 1 ms/MAX 1.2 ms, ON to OFF: TYP 1 ms/MAX 1.2 ms
          [Input time constant setting 10 ms] OFF to ON: TYP 10 ms/MAX 12 ms, ON to OFF: TYP 10 ms/MAX 12 ms
          (4-stage switching)

          Input impedance

          5.6 kΩ

          Internal current consumption

          25 mA or less

          Weight

          Approx. 140 g

          *1 Connectors for connector-type I/O units are not included. MIL34-pin slender connector kit OP-42224 and MIL34-pin connector kit OP-23139 are available separately.
          *2 All terminals are compatible with the 2-wire system (However, EV Series 2-wire system proximity sensors are not supported).
          *3 Although KV-C64XC has four common points, the H side (2 points) are the same, and the L side (2 points) are the same as internal points.
          *4 Setup is only possible when KV-7500/7300/5500/5000/3000 is connected. When KV-1000/700 is connected, selection is not possible.