Compact Switching Power Supply

MS2 series

Catalogues View Catalogue

This model has been discontinued.
Compliance with the certification standard is ensured as of the time of shipment from our company.

Output Current 4.5 A, 100 W MS-H100

MS-H100 - Output Current 4.5 A, 100 W

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Data Sheet (PDF)

Manuals

CAD / CAE

360°view (3D PDF)

Specifications

Model

MS-H100

Input conditions

Input voltage

85 to 264 VAC (50/60 Hz), 120 to 340 VDC*1

Frequency

47 to 63 Hz, DC*2

Inputconditions

Input current (100/200 VAC)

1.6/0.9A or less

Power factor (100/200 VAC)

0.99, 0.95 (typ.) at maximum load

Efficiency (100/200 VAC)

76 to 81% typ.

Leakage current (100/200 VAC)

0.4/0.75mA or less

Rush current (100/200 VAC)

18, 36 A or less (with a +25°C cold start)

Output characteristics

Rated voltage

24V

Variable voltage range

4.5A

Rated current

Ripple/noise voltage

1% (p- p) or less

Input fluctuation

0.4% or less

Load fluctuation

0.7% or less

Startup time

1300/700ms or less (AC100/200V)*3

Output holding time

20 ms min. (100 to 240 VAC)

Protection

Overcurrent protection

5.3 A or more

Overvoltage protection

Present*4

Display

Display power

2-digit 7-segment LED (character height: 10 mm)

Power off memory time

Approx. 10 years (at 20°C)

Display resolution

0.1A

Applicable standards

Safety standards

UL1950, UL1012, CSA C22.2 No.95095, EN60950, EN50178

EMC standard

FCC Part 15 B Class A, EN55011 Class A

Limits for harmonic current emissions

EN61000-3-2

Environmental resistance

Insulation resistance

100 MΩ min. (with 500 VDC megohmmeter)
(across input and output terminals) (across input terminals and PE terminal)

Ambient temperature

-10 to +55 °C (No freezing) (See "Output conditions".)

Relative humidity

25 to 85 % RH (No condensation)

Storage temperature

-20 to +70 °C (No freezing)

Withstand voltage

3.0 kVAC, 50/60 Hz, 1 min (across input and output terminals)
2.0 kVAC, 50/60 Hz, 1min (across input terminals and PE terminal)
500 VAC, 50/60 Hz, 1min (across output terminals and PE terminal)

Vibration resistance

10 to 55 Hz, Double amplitude 1.5 mm or less, 2 hours in each of the X, Y, and Z directions
(1 G when attached to a DIN rail)

Shock resistance

300 m/s2, 2 times for each direction of 3 axes

Weight

Approx. 560 g

*1 When applying for safety standards are 100 to 240 VAC, 50/60 Hz.
*2 The rated input voltage and rated frequency when applying for safety standards are 100 to 240 VAC, 50/60 Hz.
*3 Defined with a rated input voltage of 100 VAC or 200 VAC at 100% load.
*4 The H Series is a cutoff type. To return, turn OFF the input power supply and after leaving it off for 1 minute or more, plug in the input power supply again. The E/F Series is a Zener diode clamp type. It will not restart after the protection circuit operation.

Data Sheet (PDF) Other Models