Expansion Output Unit 8-output Relay connector type KV-NC8ER

KV-NC8ER - Expansion Output Unit 8-output Relay connector type

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Data Sheet (PDF)

Manuals

CAD Data

360°view (3D PDF)

Software

  • CE Marking
  • UL Listing(c/us)

Specifications

Model

KV-NC8ER

Expansion output unit

External connectionmethod

Relay

External connection method

European terminal block

Rated load

250 VAC/30 VDC, 2 A

Leakage current (when output is OFF)

Residual voltage (at ON)

ON resistance

50mΩ or less

Common method

4 points/1 common (8 terminals)*1

Response time

OFF to ON

10 ms or less

ON to OFF

Relay life

Electrical : 100,000 cycles or more (20 cycles/minute) Mechanical : 20,000,000 cycles or more

Relay replacement

Not possible

Internal current consumption

70 mA or less

Weight

Approx. 130 g

*1 The KV-NC8ER has four C0s and four C1s, and each set of C0s and C1s is shorted internally.(The sets of C0s and C1s are independent.)