Programmable Logic Controller

KV-8000 series

Catalogues View Catalogue

European Terminal Block Type I/O Unit Input: 16 points Transistor (sink) Output: 16 points KV-NC16EXTE

KV-NC16EXTE - European Terminal Block Type I/O Unit Input: 16 points Transistor (sink) Output: 16 points

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Data Sheet (PDF)

Manuals

CAD Data

360°view (3D PDF)

Software

  • CE Marking
  • UL Listing(c/us)

Specifications

Model

KV-NC16EXTE

Expansion input unit

External connection method

European Terminal Block

Input Points

16

Input terminals

24 VDC mode

Maximum input voltage

26.4 VDC

Input rated voltage

24 VDC mode

24 VDC/3.7 mA

Minimum ON voltage

19 V

Maximum OFF voltage

1.5 mA

Common method

16 points/1 common (1 terminal) *1

Input time constant (four-level switching)

Input time constant setting

OFF to ON: Typ.

25 μs: 10 μs
300 μs: 240 μs
1 ms: 1 ms
10 ms: 10 ms

OFF to ON: Max.

25 μs: 50 μs
300 μs: 290 μs
1 ms: 1.2 ms
10 ms: 11 ms

ON to OFF: Typ.

25 μs: 50 μs
300 μs: 280 μs
1 ms: 1 ms
10 ms: 10 ms

ON to OFF: Max.

25 μs: 150 μs
300 μs: 390 μs
1 ms: 1.2 ms
10 ms: 11 ms

Input impedance

6.2 kΩ

Expansion output unit

External connection method

European Terminal Block

Output Points

16

External connectionmethod

MOSFET (N-ch; with overcurrent protection function) *2

Rated load

30 VDC, 0.2 A *3

Leakage current (when output is OFF)

100 μA or less

Residual voltage (at ON)

0.6 VDC or less

Common method

16 points/1 common (1 terminal) *1

Response time

OFF to ON

100 μs or less (with a load of 1 mA or more)

ON to OFF

200 μs or less (with a load of 1 mA or more)

Internal current consumption

30 mA or less

Weight

Approx. 120 g

*1 The input COM and output COM terminals are independent.
*2 If even a single overcurrent is detected, until the cause of the problem is removed, the protection operation (output turning OFF) and automatic recovery occur repeatedly for all outputs within the shared common.
*3 The rated load per common1 terminal for KV-NC16EXT/KV-NC32EXT is 1.6A. The rated load per common1 terminal for KV-NC16EXTE is 3.2A.

Data Sheet (PDF) Other Models