Programmable Logic Controller
KV Nano series
Specs Programmable Logic Controller KV Nano series
Connector type: Expansion input unit
Model |
KV-NC16EXE |
|||
Image |
|
|||
Expansion input unit |
External connection method |
European terminal block |
||
Input Points |
16 points |
|||
Input terminals |
24 VDC mode, 5 VDC mode |
|||
Maximum input voltage |
26.4 VDC |
|||
Input rated voltage |
24 VDC mode |
5.2 mA |
||
5 VDC mode |
1 mA |
|||
Minimum ON voltage |
24 VDC mode |
19 V |
||
5 VDC mode |
3.5 V |
|||
Maximum OFF voltage |
24 VDC mode |
1.5 mA |
||
5 VDC mode |
1.5 V |
|||
Common method |
16 points/1 common (16 terminals) *1 |
|||
Input time constant (four-level switching) |
Input time constant setting |
OFF to ON: Typ. |
25 µs: 10 µs |
|
OFF to ON: Max. |
25 µs: 50 µs |
|||
ON to OFF: Typ. |
25 µs: 50 µs |
|||
ON to OFF: Max. |
25 µs: 150 µs |
|||
Input impedance |
4.4 kΩ |
|||
Internal current consumption |
20 mA or less |
|||
Weight |
Approx. 120 g |
|||
*1 The KV-NC16EXE has 16 COM terminals, but these are shared internally. |
Connector type: Expansion ounput unit
Model |
KV-NC16ETE |
KV-NC16ETPE |
|||
Image |
|
|
|||
Expansion output unit |
External connectionmethod |
MOSFET output (With overcurrent protection function)*1*2 |
|||
External connection method |
European terminal block |
||||
Rated load |
30 VDC, 0.2 A*3 |
||||
Leakage current (when output is OFF) |
100 µA or less |
||||
Residual voltage (at ON) |
0.6 VDC or less |
||||
ON resistance |
― |
||||
Common method |
16 points/1 common (16 terminals)*4*5 |
||||
Response time |
OFF to ON |
100 µs or less (with a load of 1 mA or more) |
|||
ON to OFF |
200 µs or less (with a load of 1 mA or more) |
||||
Relay life |
― |
||||
Relay replacement |
|||||
Internal current consumption |
30 mA or less |
||||
Weight |
Approx. 120 g |
||||
*1 If even a single overcurrent is detected, the protection operation (output turned OFF) and automatic recovery are repeated for all outputs within the shared common (The outputs within the shared common that are protected when an overcurrent is detected are outputs 000 to 007 or 008 to 015 for the KV-NC16ET(P) and KV-NC16ET(P)E.), until the cause of the problem is removed. |