Recent Searches
    Series ()
      Models ()
        Keywords

          Programmable ControllerKV-5000/3000 series

          KV-C32XTD

          32-point/32-point Connector MOSFET (Sink) with Overcurrent Protection

          SPECIFICATIONS

          Select Language

          Model

          KV-C32XTD

          Type

          I/O unit

          External connection mode

          Connector (MIL standard)*1

          Input

          Number of inputs

          32 points

          Input mode

          24 VDC mode*2

          Max. input voltage

          26.4 VDC

          Rated input voltage

          24 VDC 4.1 mA

          Min. ON voltage

          19 V

          Max. OFF current

          1.5 mA

          Max. OFF voltage

          -

          Common point mode

          32 points/1 common point (2 terminals)*3

          Input time constant

          25 µs/300 µs*4/1 ms/10 ms

          Input impedance

          5.6 kΩ

          Output

          Number of outputs

          32 points

          Output form

          MOS-FET (N ch) (with an overcurrent-proof function)

          Rated load

          30 VDC 0.2 A

          Leak current at OFF

          100 µA or less

          Residual voltage at ON

          0.5 V or less

          Common point mode

          32 points/1 common point (2 terminals)*3

          Operating time

          OFF to ON: 150 µs or less, ON to OFF: 300 µs or less

          Internal current consumption

          65 mA or less

          Weight

          Approx. 130 g

          *1 Connectors for connector-type I/O units are not included. MIL40-pin slender connector kit OP-51404 and MIL40-pin connector kit OP-22184 are available separately.
          *2 All terminals are compatible with 2-wire system (however, EV Series 2-wire system proximity sensors are not supported).
          *3 Although there are two input COMs and two output COMs, these COM pairs are the same internally. The input and output COM pairs are independent.
          *4 Setup is only possible when KV-7500/7300/5500/5000/3000 is connected. When KV-1000/700 is connected, selection is not possible.