Recent Searches
    Series ( results)
      Models ( results)
        Keywords
          1. Home
          2. Products
          3. Controls
          4. PLC(Building-block/ Modular/ High Speed type)
          5. Programmable Controller
          6. Models
          7. Connector Conversion Unit for SV

          Programmable ControllerKV-5000/3000 series

          Connector Conversion Unit for SV

          KV-HTC8

          SPECIFICATIONS

          Select Language

          Model

          KV-HTC8

          Input rating

          20 mA, 5 V; 5.3 mA, 24 V

          Output rating

          20 mA, 5 V; 50 mA, 30 V

          Safety standards

          UL508, EN61131-2

          Rating

          Power voltage

          24 VDC ±10 %

          Environmental resistance

          Insulation resistance

          50 MΩ or more
          (tested with a 500 VDC megger, between the power supply terminal and the I/O terminals and between all the external terminals and the case)

          Operating environment

          No dust or corrosive gas

          Vibration resistance

          Intermittent vibration

          Frequency:10 to 57Hz

          Amplitude : 0.075 mm*1

          Frequency:57 to 150Hz

          Acceleration : 9.8 m/s2*1

          Ambient temperature

          0 to +50 °C (No freezing)

          Storage temperature

          -20 to +70 °C

          Vibration resistance

          Continuous Vibration

          Frequency:10 to 57Hz

          Amplitude : 0.035 mm*1

          Frequency:57 to 150Hz

          Acceleration : 4.9 m/s2*1

          Relative humidity

          5 to 85 % RH (No condensation)

          Withstand voltage

          1,500 VAC for 1 minute
          (between the power supply terminal and the I/O terminals and between all the external terminals and the case)

          Noise resistance

          1,500 Vp-p, pulse width: 1 µs, 50 ns (by way of a noise simulator)

          Weight

          230 g (260 g when the board module of the second axis is added)

          *1 Conforms to JIS B 3502, IEC61131-2, 10 times respectively in the X, Y, and Z directions, 80 minutes

          • PLC/HMI User Support
          • Trade Shows and Exhibitions
          • eNews Subscribe

          Back to top

          KEYENCE INDIA PVT. LTD. SKCL Triton Square, 1st Floor, No. C3 to C7,
          Thiru-Vi-Ka Industrial Estate, Guindy, Chennai – 600032,
          Tamil Nadu, India
          Phone: 1-800-103-0090
          E-mail: info@keyence.co.in
          Career Opportunities: KEYENCE Career Site

          Controls