Recent Searches
    Series ( results)
      Models ( results)
        Keywords
          Fully Operational with Expanded Resources
          Click for the latest on how KEYENCE is continuing to support our customers with quick delivery, off-site testing, virtual demos and more.
          1. Home
          2. Products
          3. Controls
          4. PLC(Building-block/ Modular/ High Speed type)
          5. Programmable Controller
          6. Models
          7. Analog Output Unit (4-channel)

          Programmable ControllerKV-5000/3000 series

          Analog Output Unit (4-channel)

          KV-RC4DA

          SPECIFICATIONS

          Select Language

          Model

          KV-RC4DA

          General Specifications

          Power voltage

          24 VDC ± 10%

          Operating ambient temperature

          0 to +60°C (no freezing)

          Ambient temperature for storage

          -20 to +75°C

          Operating ambient humidity

          10 to 95%RH(no condensation)

          General specifications

          Storage relative humidity

          General Specifications

          Withstand voltage

          1,500 VAC for 1 minute (between the power supply terminal and the communication terminal, between the power supply terminal and the I/O terminals, and between all the external terminals and the case)

          Noise immunity

          1,500 Vp-p or more, pulse width: 1 µs, 50 ns (by way of a noise simulator), conforms to IEC standards (IEC 61131-2)

          Vibration resistance

          Intermittent vibration

          Frequency:5 to 9Hz

          Half amplitude: 3.5 mm*1

          Frequency:9 to 150Hz

          Acceleration: 9.8 m/s2*1

          Continuous Vibration

          Frequency:5 to 9Hz

          Half amplitude: 1.75 mm*1

          Frequency:9 to 150Hz

          Acceleration: 4.9 m/s2*1

          Insulation resistance

          50 MΩ or more (tested with a 500 VDC megger, between the power supply terminal and the I/O terminal)

          Operating environment

          Minimal amount of dust and corrosive gas present

          Altitude

          2000m or less

          General specifications

          Current consumption

          240mA

          Approved standards

          Overvoltage category

          I

          Pollution degree

          2

          CE marking

          EMI :EN55011 Class A
          EMS :EN61131-2

          FCC

          FCC Part15B class A

          UL

          UL :UL508
          CSA :CAN/CSA22、2 No.14

          ICES

          ICES-003 Issue4

          Enclosure rating

          IP2X

          CC-Link specifications

          Supported versions: 2.00, 1.10; number of occupied stations: 1 station ×2 with version 2.00, 2 stations with version 1.10; station type: remote device station

          Performance specifications

          Analogue output point

          4

          Analogue output range (resolution)

          Voltage: -10 to 10 V (0.83 mV, 1/24000)
          0 to 10 V (0.83 mV, 1/12000)
          -5 to 5 V (0.42 mV, 1/24000)
          0 to 5 V (0.42 mV, 1/12000)
          1 to 5 V (0.42 mV, 1/9600)
          current: 0 to 20 mA (1.67 µA, 1/12000)
          4 to 20 mA (1.67 µA, 1/9600)

          Minimum load resistance

          Voltage: 1 kΩ

          Maximum load resistance

          Current: 400 Ω

          Weight

          approx 200g

          *1 Conforms to JIS B 3502 IEC61131-2
          Number of sweeps: 10 times respectively in the X, Y, and Z directions, 100 minutes

          • PLC/HMI User Support
          • Trade Shows and Exhibitions
          • eNews Subscribe

          Back to top

          KEYENCE INDIA PVT. LTD. SKCL Triton Square, 1st Floor, No. C3 to C7,
          Thiru-Vi-Ka Industrial Estate, Guindy, Chennai – 600032,
          Tamil Nadu, India
          Phone: 1-800-103-0090
          E-mail: info@keyence.co.in
          Career Opportunities: KEYENCE Career Site

          Controls