Recent Searches
    Series ( results)
      Models ( results)
        Keywords
          Fully Operational with Expanded Resources
          Click for the latest on how KEYENCE is continuing to support our customers with quick delivery, off-site testing, virtual demos and more.
          1. Home
          2. Products
          3. Controls
          4. PLC(Building-block/ Modular/ High Speed type)
          5. Programmable Controller
          6. Models
          7. Temperature Analog Multi-input Unit (Multi-input 4-channel)

          Programmable ControllerKV-5000/3000 series

          Temperature Analog Multi-input Unit (Multi-input 4-channel)

          KV-TP40

          SPECIFICATIONS

          Select Language

          Model

          KV-TP40

          Type

          Temperature and analogue multi-input unit

          Number of temperature input points

          4 ch

          Input

          Thermocouple/Platinum temperature measuring resistor/Voltage and current

          Input range

          Thermocouple

          K: -270.0 to 1,372.0 °C
          J: -210.0 to 1,200.0 °C
          T: -270.0 to 400.0 °C
          E: -270.0 to 1,000.0 °C
          N: -270.0 to 1,300.0 °C
          R: -50.0 to 1,768.0 °C
          S: -50.0 to 1,768.0 °C
          B: 0.0 to 1,820.0 °C
          WRe5-26: 0.0 to 2,315.0 °C

          Platinum temperature measuring resistor

          Pt100: -200.0 to 850.0 °C
          JPt100: -200.0 to 600.0 °C

          Voltage and current

          Voltage:
          -10 to +10 V (0.5 mV 1/40,000)
          0 to 10 V (0.5 mV 1/20,000)
          -5 to +5 V (0.5 mV 1/20,000)
          0 to 5 V (0.5 mV 1/10,000)
          1 to 5 V (0.5 mV 1/8,000)
          -100 to +100 mV (5 µV 1/40,000)
          0 to 100 mV (5 µV 1/20,000)
          Current:
          0 to 20 mA (2 µA 1/10,000)
          4 to 20 mA (2 µA 1/8,000)

          Indicated accuracy

          ±0.2 % of F.S. (25 ±5 °C), ±0.4 % of F.S. (0 to 50 °C)

          Cold junction correction precision

          ±1 °C (during thermocouple input)

          Conversion speed

          50 ms/4 ch

          Insulation mode

          Between an input terminal and CPU: Photocoupler transformer insulation,
          Between channels: Photocoupler transformer insulation

          Other functions

          External cold junction correction, wire-breaking detection function, scaling function,
          average processing function (time average, average of the number of times, moving average, primary delay filter)
          Special data offset function, alarm function, rate of change calculation, rate of change alarm function

          Internal current consumption

          90 mA or less

          Weight

          Approx. 190 g

          • PLC/HMI User Support
          • Trade Shows and Exhibitions
          • eNews Subscribe

          Back to top

          KEYENCE INDIA PVT. LTD. SKCL Triton Square, 1st Floor, No. C3 to C7,
          Thiru-Vi-Ka Industrial Estate, Guindy, Chennai – 600032,
          Tamil Nadu, India
          Phone: 1-800-103-0090
          E-mail: info@keyence.co.in
          Career Opportunities: KEYENCE Career Site

          Controls