Programmable Logic Controller
KV-X series
EtherCAT® Compatible Communication Unit KV-EC01
*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.
Specifications
Model | KV-EC01 | |||
General specifications | Power voltage | 24V DC (+10%/-15%) | ||
Operating ambient temperature | 0 to 55ºC (no freezing) *1 *2 | |||
Operating ambient humidity | Up to 95%RH (no condensation) *1 | |||
Ambient temperature for storage | -25 to 75ºC (no freezing) *1 | |||
Storage relative humidity | Up to 95%RH (no condensation) *1 | |||
Operating environment | No excessive dust and corrosive gases | |||
Altitude | 2000m or less | |||
Noise immunity | Conforms to IEC standards (IEC61000, 4-2/3/4/6) | |||
Withstand voltage | 1500 V AC for 1 minute, between power supply terminal and I/O | |||
Insulation resistance | 50 MΩ or more (500V DC megger used to perform measurements between power terminal and input terminals, and between all external terminals and case) | |||
Vibration resistance | Intermittent vibration | Frequency 5 to 9 Hz | Amplitude: 3.5mm *3 *4 | |
Frequency 9 to 150 Hz | Acceleration: 9.8 m/s2 *3 *4 | |||
Continuous vibration | Frequency 5 to 9 Hz | Amplitude: 1.75mm *3 *4 | ||
Frequency 9 to 150 Hz | Acceleration: 4.9 m/s2 *3 *4 | |||
Internal current consumption (excluding current for driving input circuits) | 120mA or less *5 | |||
Shock resistance | Acceleration: 150m/s2, Application time: 11ms, Tree times in each of the X, Y, and Z directions. *3 | |||
Overvoltage category | Ⅰ | |||
Pollution degree | 2 | |||
Weight | Approx. 110g | |||
Performance specifications | Connection interface | RJ-45 8-poles modular connector x 2PORT | ||
Transmission rate | 100Mbps (100BASE-TX) *6 | |||
Transmission media | UTP (Category 5 or above) or STP (STP recommended) *7 | |||
Max. cable length | 100m | |||
EtherCAT Specifications | Device profile | CoE | ||
Supported functions | Process data objects communication | |||
Supported modes | SyncManager, Distributed Clock | |||
*1 Guarantee range as a system |