Expansion Input Unit 32-input switching 5V/24V DC connector type KV-NC32EX

KV-NC32EX - Expansion Input Unit 32-input switching 5V/24V DC connector type

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Data Sheet (PDF)

Manuals

CAD Data

360°view (3D PDF)

Software

  • CE Marking
  • UL Listing(c/us)

Specifications

Model

KV-NC32EX

Expansion input unit

External connection method

Connector

Input Points

32 points

Input terminals

24 VDC mode, 5 VDC mode

Maximum input voltage

26.4 VDC

Input rated voltage

24 VDC mode

5.2 mA

5 VDC mode

1 mA

Minimum ON voltage

24 VDC mode

19 V

5 VDC mode

3.5 V

Maximum OFF voltage

24 VDC mode

1.5 mA

5 VDC mode

1.5 V

Common method

32 points/1 common (2 terminals)*1

Input time constant (four-level switching)

Input time constant setting

OFF to ON: Typ.

25 µs: 10 µs
300 µs : 240 µs
1 ms: 1 ms
10 ms: 10 ms

OFF to ON: Max.

25 µs: 50 µs
300 µs : 290 µs
1 ms: 1.2 ms
10 ms: 11 ms

ON to OFF: Typ.

25 µs: 50 µs
300 µs : 280 µs
1 ms: 1 ms
10 ms: 10 ms

ON to OFF: Max.

25 µs: 150 µs
300 µs : 390 µs
1 ms: 1.2 ms
10 ms: 11ms

Input impedance

4.4 kΩ

Internal current consumption

20 mA or less

Weight

Approx. 110 g

*1 The KV-NX16EX and KV-NC32EX have 2 COM terminals, but these are shared internally.